UPS reference diagram Current location: Home > Technical support > UPS reference diagram  

UPS reference table

UPS power output and the discharge time (minutes) :

1. Ambient temperature (25 oc)

2. The nominal voltage of the battery pack 48 V and 96 V

3. The lowest electricity county. 8 v/single

4. Not considering power compensation factor

型号

Volts

300VA

500VA

1KVA

2KVA

3KVA

5KVA

7.5KVA

10KVA

15KVA

20KVA

SJ6V4.5Ah

48V

17

7

96V

46

23

7

SJ6V5Ah

48V

28

14

96V

62

35

1.4

SJ6V7.2Ah

48V

39

19

5

96V

90

49

19

5

SJ6V10Ah

48V

62

31

8.5

96V

140

78

31

8.5

SJ6V12Ah

48V

72

38

15

96V

170

92

38

15

6.6

SJ12V4.2Ah

48V

17

7

96V

46

23

7

SJ12V5Ah

48V

28

14

96V

62

35

1.4

SJ12V7Ah

48V

39

19

5

96V

90

49

19

5

SJ12V18Ah

48V

61

22

5.6

96V

61

22

10

SJ12V24Ah

48V

39

12

5

96V

100

39

20

7.5

SM12V33Ah

48V

50

22

13

6

96V

120

50

30

15

11

SM12V38Ah

48V

75

26

13

4

96V

75

40

18

8.6

SM12V65Ah

48V

50

28

12

5

96V

79

35

19

SM12V100Ah

48V

58

25

11

5

96V

120

68

40

25

11

SM12V120Ah

48V

70

30

15

8

96V

82

50

29

15

8

SM12V150Ah

48V

50

22

13

7

96V

100

75

50

22

10

SM12V200Ah

48V

45

20

12

6

96V

110

80

45

20

 

 
Copyright © Guangzhou Ouji Electronic Technology Co., Ltd All Rights Reserved.
Address: Guangzhou City, Panyu District Qinghe Road No. 76 east Shi Gang Tel:020-34628335 Fax:020-34628335 Code:510640
Url: http://www.ibmabb.com E-mail: 2397808949@qq.com